UPS Products

Embedded with isolation transformer, iON G3PRO 40-120KVA series will eliminate common mode noise and the need to install expensive dedicated circuits. It provides reliable galvanically isolated power to critical equipment.

 

 

 

 

 

 



OnLine UPS

iON G3PRO 40K / iON G3PRO 60K
iON G3PRO 80K / iON G3PRO 120K

  • Model iON G3PRO 40K iON G3PRO 60K iON G3PRO 80K
    iON G3PRO 120K
    Phase 3-phase in / 3-phase out
    Capacity 40000 VA / 32000 W 60000 VA / 48000 W 80000 VA / 64000 W 120000 VA / 96000 W
    INPUT
    Nominal Voltage 3 x 380VAC/400VAC (3Ph + N)
    Acceptable Voltage Range 285VAC ~ 475VAC
    Frequency 50/60 Hz ± 10 %
    INVERTER
    Output Voltage 3 x 380VAC/400VAC (3Ph + N)
    Precision
    Stationary: ±1%
    Transitory: ±5% (load variations 100-0-100%)
    Frequency
    50/60 Hz synchronised ±1 %
    With mains absent ±0.1 Hz
    Max. Synchronisation
    Speed
    ±1 Hz/s
    Waveform Pure Sinewave
    Total Harmonic Distortion
    (THDv)
    <2% (Linear Load) ; <5% (Non-linear Load)
    Phase Displacement 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load)
    Dynamic Recovery Time 3 cycles at 90 % of the static value
    Admissible Overload 110% for 10min; 150% for 60sec ; >160% for 200ms
    Admissible Crest Factor 3:1
    Admissible Power Factor 0.6~1 (inductive or capacitive)
    Imbalance Output Voltage
    @ 100% Unbalanced Load
    <1%
    Current Limit
    High overload, short-circuit: RMS Voltage Limit
    High Crest-Factor current: Peak Voltage Limit
    STATIC BYPASS
    Type Solid state
    Voltage 3 x 380VAC/400VAC (3Ph + N)
    Frequency 50/60 Hz
    Activation Criterion Microprocessor control
    Transfer Time Zero
    Admissible Overload 150% for 1 hour; 180% for 30sec; >200% for 200ms
    Transfer to Bypass Immediate, for overloads above 160%
    Retransfer Automatic after alarm clear
    MAINTENANCE BYPASS
    Type Without interruption
    Voltage 3 x 400V (3Ph + N)
    Frequency 50/60 Hz
    Overall
    Efficiency
    Line Mode 92% 92% 93% 93%
    Battery Mode 93% 93% 93% 93%
    BATTERY & CHARGER
    Battery Type and Numbers 12VDC x 32 pcs (29~32 pcs adjustable)
    Nominal Battery Voltage 384 VDC (Based on 32pcs batteries)
    Charging Method CC/CV
    Charging Current Default: 10A. Max. 40A
    Charging Voltage 432 VDC (Based on 32pcs batteries)
    PHYSICAL
    Dimensions,
    D x W x H (mm)
    821 x 432 x 1159 975 x 554 x 1286 975 x 554 x 1286
    975 x 635 x 1326
    Net Weight (Kgs) 278 400 471 650
  • Main Features

       * Online double-conversion
       * DSP technology guarantees high reliability
       * True galvanic isolation transformer design
       * Control designed to withstand all kinds of loads
       * Intelligent battery management to prolong battery lifecycle
       * Redundant fan design and independent ventilation enhance durable operation under harsh environment
       * Adjustable battery numbers
       * Accept dual-mains input
       * Parallel operation with up to 4 units (option)
       * Variety of communication options available
       * Optional 7" touch LCD