Designed in small footprints, iON G3PRO online series integrates true double conversion design, DSP technology, and active input power factor correction design to ensure better output voltage conditions, power quality and power performance at all times. Besides, easy-configurable program via LCD panel enhances the flexibility to meet ever-increasing power demand of IT and networked environment.

 



OnLine UPS

iON G3PRO 10K / iON G3PRO 15K
iON G3PRO 20K / iON G3PRO 30K

 

  • Model iON G3PRO 10K iON G3PRO 15K iON G3PRO 20K
    iON G3PRO 30K
    Phase 3-phase in / 3-phase out
    Capacity 10000 VA / 8000 W 15000 VA / 12000 W 20000 VA / 16000 W 30000 VA / 24000 W
    INPUT
    Nominal Voltage 3 x 400 VAC (3Ph+N)
    Input Voltage Range 305-478 VAC (3-phase) at 100% load ; 190-520 VAC (3-phase) at 50% load
    Frequency Range 46~54 Hz or 56~64Hz
    Power Factor ≧ 0.99 @ 100% Load
    OUTPUT
    Output Voltage 3 x 400 VAC (3Ph+N)
    AC Voltage Regulation (Batt. Mode) ± 1%
    Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
    Frequency Range (Bat.Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
    Current Crest Ratio 3:1 (max.)
    Harmonic Distortion ≦ 2 % THD (Linear Load) ; ≦ 5 % THD (Non-linear Load)
    Transfer
    Time
    AC Mode to Bat. Mode Zero
    Inverter to Bypass Zero
    Waveform (Batt. Mode) Pure Sinewave
    EFFICIENCY
    AC Mode 89% 89% 89% 90%
    Battery Mode 86% 88% 87% 89%
    BATTERY
    Battery Type & Number Battery Type 12 V / 9 Ah
    Numbers 20 pcs (18 - 20 adjustable)* 20 pcs x 2 strings (18 - 20 adjustable)* 20pcs x 3 strings(18-20 adjustable)*
    Typical Recharge Time 9 hours recover to 90% capacity
    Charging Current (Max.) 1A 2A 2A 4A
    Charging Voltage 273 VDC ± 1%
    Typical Recharge Time Battery Type Depending on the capacity of external batteries
    Numbers  
    Charging Current (Max.) 4A 4A 4A 12A
    Charging Voltage 273 VDC ± 1%
    PROTECTION
    Full Protection Overload, discharge, and overcharge protection
    INDICATORS
    LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault
    ALARM
    Battery Mode Sounding every 4 seconds
    Low Battery Sounding every second
    Overload Sounding twice every second
    Fault Continously sounding
    PHYSICAL
    Standard Model Dimension, DxWxH (mm) 815 x 250 x 826 815 x 250 x 826 815 x 250 x 826 815 x 300 x 1000
    Net Weight (kgs)  109 164 164 233.5 
    Long-run Model Dimension, DxWxH (mm)  592 x 250 x 826 592 x 250 x 826  592 x 250 x 826  815 x 250 x 826 
    Net Weight (kgs) 38 40 40 64
    ENVIRONMENT
    Humidity 0-95 % RH @ 0- 40°C (Non-condensing)
    Noise Level Less than 60dB @ 1 Meter Less than 65dB @ 1 Meter
    MANAGEMENT
    Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix, and MAC
    Optional SNMP Power management from SNMP manager and web browser
  • Main Features

       * True double-conversion
       * DSP technology guarantees high performance
       * Output power factor 0.8
       * Wide input voltage range (110-300 VAC)
       * Active power factor correction in all phases
       * 50Hz/60Hz frequency converter mode
       * ECO mode operation for energy saving
       * Accepts dual-mains inputs
       * Emergency power off function (EPO)
       * Generator compatible
       * SNMP+USB+RS-232 multiple communications
       * 3-stage extendable charging design for optimized battery performance
       * Adjustable battery numbers
       * Maintenance bypass available
       * Optional N+X parallel redundancy
       * Optional isolation transformer offers full isolation and complete common mode noise rejection