With true double-conversion design, G (Rackmount) series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. It's perfect protection for your precious servers and workstations.


OnLine UPS

iON GRM-1K / iON GRM-2K / iON GRM-3K / iON GRM-10K

  • Model iON G-RM-1K
    iON G-RM-2K iON G-RM-3K iON G-RM-10K
    PHASE Single phase with ground
    Capacity 1000 VA / 800 W 2000 VA / 1600 W 3000 VA / 2400 W 10000 VA / 8000 VA
    INPUT
    Nominal Voltage 100/110/115/120/127 VAC or 200/208/220/230/240VAC 208/220/230/240 VAC
    Voltage Range 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load
    80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load
    110-300 VAC at 50% load
    176-300 VAC at 100% load
    Frequency Range 45Hz ~ 55 Hz or 56Hz ~ 65 Hz 46~54 Hz or 56~64 Hz
    Power Factor ≧ 0.99 @ Nominal Voltage (100% Load) ≧ 0.99 @ 100% load
    OUTPUT
    Output Voltage 100/110/115/120/127 VAC or 200/208/220/230/240VAC 208/220/230/240 VAC

    AC Voltage Regulation    (Batt. Mode)

    ± 1%
    Frequency Range (Synchronized Range) 40 Hz ~ 70 Hz 46~54 Hz or 56~64 Hz
    Frequency Range     (Batt. Mode) 50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz

    50 Hz ± 0.1 Hz

    or 60 Hz ± 0.1 Hz

    Current Crest Ratio 3:1
    Harmonic Distortion ≦ 3 % THD (Linear Load),
    ≦ 6 % THD (Non-Linear load)
    Transfer
    Time
    AC Mode to Bat. Mode Zero
    Inverter to Bypass 4 ms (Typical) Zero
    Waveform (Batt. Mode) Pure Sinewave
    EFFICIENCY
    AC Mode 86% 87% 88% 89%
    Battery Mode 84% 85% 86% 88%
    BATTERY
    Battery Type
    12 V / 9 Ah 12 V / 9 Ah 12 V / 9 Ah  12 V / 9 Ah
    Number 2 4 6 20
    Typical Recharge Time 4 hours recover to 90% capacity
    Charging Current (Max.) 1.0 A 2.0 A
    Charging Voltage 27.4 VDC ± 1% 41.1 VDC ± 1% 82.1 VDC ±1% 273.0 VDC ±1%
    INDICATORS
    LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
    ALARM
    Battery Mode Sounding every 4 seconds
    Low Battery Sounding every second
    Overload Sounding twice every second
    Fault Continuously sounding
    PHYSICAL
    Dimension, D x W x H (mm) 380 x 438 x 88 [2U] 480 x 438 x 88 [2U]  600 x 438 x 88 [2U] UPS Unit:
    668 x 438 x 133 [3U]
    Battery Pack :
    580 x438 x 133 [3U]
    Net Weight (kgs) 13.2 20.6 29 UPS Unit : 20
    Battery Pack : 63
    ENVIRONMENT
    Humidity 20-90 % RH @ 0- 40°C (Non-condensing)
    Noise Level Less than 50dB @ 1 Meter
    MANAGEMENT
    Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux, Unix, and MAC
    Optional SNMP Power management from SNMP manager and web browser
  • Main Features

       * True double-conversion online UPS
       * Wide input voltage range (110-300 VAC)
       * Input power factor correction 0.99
       * Output power factor 0.8
       * 50Hz/60Hz frequency converter mode
       * Programmable power management outlets
       * Emergency power off function (EPO)
       * ECO mode operation for energy saving (ECO)
       * SNMP+USB+RS-232 multiple communications
       * Smart battery charger design for optimized battery performance
       * Selectable output voltage via LCD panel
       * Optional isolation transformer offers full isolation and complete common mode noise rejection
       * Hot-swappable battery design (only available for 1-3K)