With true double-conversion design, iON G Series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. It's perfect protection for your precious servers and workstations.



OnLine UPS

iON G-1000 LCD / iON G-2000 LCD
iON G-3000 LCD/ iON G-6000 LCD / iON G-10000 LCD

  • Model iON G-1000 LCD iON G-2000 LCD iON G-3000 LCD iON G-6000 LCD
    iON G-10000 LCD
    Phase Single phase with ground
    Capacity 1000 VA / 800 W 2000 VA/1600 W 3000 VA / 2400 W 6000 VA / 4800 W 10000 VA / 8000 W
    INPUT
    Nominal Voltage 200/208/220/230/240 VAC or 100/110/115/120/127 VAC 208/220/230/240 VAC
    Voltage Range 55-150 VAC ± 5 % or 110-300 VAC ± 5 % at 50% load
    80-150 VAC ± 5 % or 160-300 VAC ± 5 % at 100% load
    110-300 VAC at 50% load
    176-300 VAC at 100% load
    Frequency Range 40 Hz ~ 70 Hz 46 ~ 54 Hz or 56 ~ 64 Hz
    Power Factor >= 0.99 @ Nominal Voltage (100% Load)
    OUTPUT
    Output Voltage 200/208/220/230/240 VAC or 100/110/115/120/127 VAC 208/220/230/240 VAC
    AC Voltage Regulation ± 1%
    Frequency Range
    47~53 Hz or 57~63 Hz
    Frequency Range (Bat.Mode) 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
    Current Crest Ratio 3:1
    Harmonic Distortion ≦2 % THD (Linear Load)
    ≦ 4 % THD (Non-linear Load)
    ≦ 3 % THD (Linear Load)
    ≦ 6 % THD (Non-linear Load)
    Transfer
    Time
    AC Mode to Bat. Mode Zero
    Inverter to Bypass 4 ms (Typical) Zero
    Waveform (Batt. Mode) Pure Sinewave
    EFFICIENCY
    AC Mode 87% 90% 89%
    Battery Mode 83% 87% 88%
    BATTERY
    Battery Type 12 V/7 Ah
    12 V / 7 Ah 12 V/9 Ah
    12 V/7 Ah
    12 V/9 Ah
    Number 3 6 6 20 20
    Typical Recharge Time 4 hours recover to 90% capacity 7 hours recover to 90% capacity 9 hours recover to 90% capacity
    Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1% 82.0 VDC ± 1% 273.0 VDC ±1%
    PROTECTION
    Full Protection Overload, discharge, and overcharge protection
    INDICATORS
    LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
    ALARM
    Battery Mode Sounding every 4 seconds
    Low Battery Sounding every second
    Overload Sounding twice every second
    Fault Continuously sounding
    PHYSICAL
    Dimension, D x W x H (mm) 397 x 145 x 220 421 x 190 x 318 421 x 190 x 318 592 x 250 x 576 
    Net Weight (kgs) 13 26 28 81 83
    ENVIRONMENT
    Humidity 20-90 % RH @ 0- 40°C (Non-condensing)
    Noise Level Less than 50dB@1Meter Less than 55dB@1Meter Less than 58dB@1Meter
    MANAGEMENT
    Optional USB/RS-232 Port Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix, and MAC
    Optional SNMP Power management from SNMP manager and web browser
  • Main Features

       * True double-conversion online UPS
       * Output power factor 0.8
       * Wide input voltage range (110 V -300 V)
       * Programmable power management outlets
       * 50/60 Hz Frequency Converter Mode
       * ECO mode operation for energy saving
       * Emergency Power Off (EPO) Function
       * SNMP+USB+RS-232 multiple communications for 1-3K models
       * DSP technology applied for 6K and up models
       * Smart battery charger design to optimize battery performance
       * Maintenance bypass available for 6K and up models
       * Optional hot standby mode and N+X parallel redundancy available for 6K and up models
       * Adjustable battery numbers for 6K and up models
       * Built-in isolation transformer (Option)